+86 18068001229 Tilmaamaha Farsamada ee Ogaanshaha Isbeddelka Beddelka Beddelka Korontada Sare
Xalalka Is-beddelka JZP
- Hordhac
Isbeddelka wareegga ee heerka sare ahBeddelayaasha Danabka waa walaac badbaado oo muhiim ah, oo badanaa ay sababaan cadaadis farsamo, wareeg kulayle, ama saameyn wareeg gaaban. Iyada oo ah hormuudka wax soo saarka transformers-ka, JZP waxay u hoggaansamaysaa Heerka DL/T 1093-2018 ee Habka Falcelinta ee Ogaanshaha Isbeddelka Wareegga waxayna isku daraysaa teknoolojiyadaha horumarsan si loo hubiyo u hoggaansanaanta iyo isku halaynta. Dukumentigan wuxuu qeexayaa qeexitaannada farsamo ee JZP ee ogaanshaha isbeddelka wareegga, oo daboolaya hababka, shuruudaha qalabka, iyo hababka hawlgalka.
- Baaxadda
Qeexitaankani wuxuu khuseeyaa:
Kala duwanaanshaha danabka: 35 kV iyo wixii ka sareeya.
Noocyada Transformers-ka: Saddex-waji iyo hal-waji Transformers-ka Awoodda oo leh qaab-dhismeedyo wareegsan.
Xaaladaha ogaanshaha: Aqbalaadda warshadda, kormeerka gaadiidka kadib, iyo qiimeynta dhacdooyinka wareegga gaaban kadib.
- Hababka Muhiimka ah ee Ogaanshaha
3.1 Habka Falcelinta (U hoggaansanaanta DL/T 1093-2018)
Mabda': Waxay cabbirtaa isbeddellada ku yimaada falgalka wareegga (impedance) ee hoos yimaada danabka AC si loo ogaado qallooca farsamada.
Xuduudaha Muhiimka ah:
Inta jeer ee soo noqnoqoshada: 10 Hz – 1 MHz.
Saxnaanta: ±0.5% qiimayaasha impedance.
Danabka tijaabada: ≤2 kV (AC).
Faa'iidooyinka: Xasaasiyadda sare ee isbeddellada yaryar (tusaale ahaan, 0.1% isbeddelka iska caabinta waxay muujinaysaa dhibaatooyin suurtagal ah).
3.2 Falanqaynta Jawaabta Soo Noqnoqoshada (FRA)
Habka: Waxay tirtirtaa soo noqnoqoshada laga bilaabo 10 Hz ilaa 20 MHz si loo qabto astaamaha soo noqnoqoshada wareegga.
Horumarinta JZP:
Muunad-qaadis xal sare leh: 50,000 oo dhibcood oo xog ah oo loogu talagalay falanqaynta saxda ah ee qaabka hirarka.
Naqshadeynta faragelinta ka hortagga: Go'doominta indhaha iyo gaashaanka si loo yareeyo buuqa elektromagnetic-ka.
Wax soo saar: Falanqayn isbarbardhig ah oo ku saabsan muuqaallada soo noqnoqda ee taariikhiga ah iyo kuwa hadda jira si loo aqoonsado isbeddellada meelaha ugu sarreeya ee dhawaaqa (tusaale ahaan, kala duwanaanshaha >3 dB wuxuu kiciyaa digniino).
- Shuruudaha Farsamada
- Habka Tijaabada
5.1 Diyaarinta Imtixaanka Kahor
Hubinta qalabka: Hubi habaynta dareemayaasha (tusaale ahaan, gariiradaha Rogowski ee calaamadaha soo noqnoqda sare).
Xaaladda Transformer-ka: Hubi in transformer-ku uu tamar yaraaday oo uu dhulka ku dhacay.
5.2 Fulinta Tijaabada
Qaabeynta fiilooyinka:
Wareegga Koowaad: Ku dabaq calaamadda tijaabada (tusaale ahaan, danab ku-meel-gaar ah oo ka imanaya furitaanka jabka wareegga).
Wareegga labaad: Ku xidh dareemayaasha si aad u cabbirto calaamadaha la kiciyay.
Dejinta cabbiraadaha:
Tallaabooyinka baaritaanka soo noqnoqda: Qaybinta logarithmic si loo helo daboolid dhammaystiran.
Xadka kicinta: Si toos ah u hagaaji iyadoo lagu saleynayo awoodda isbeddelka (tusaale ahaan, 110 kV transformers waxay u baahan yihiin xasaasiyad 100× ah).
Helitaanka Xogta:
Qabso 200+ muunado halkii dhibic ee soo noqnoqoshada.
Bandhigga waqtiga-dhabta ah ee xagasha baaxadda/wajiga ee impedance.
5.3 Falanqaynta Imtixaanka Kadib
Baadhista otomaatiga ah:
Isbarbardhig saldhigga warshadda (tusaale ahaan, leexashada iska caabbinta > 2% waxay muujinaysaa beddelka).
Khariidaynta 3D ee qaybinta cadaadiska wareegga.
Warbixinta: Soo saar warbixinno u hoggaansanaan ah oo leh garaafyo iyo talooyin wax ku ool ah.
- Daraasad Kiis: Transformer-ka Beeraha Dabaysha
Xaalad: Transformer beerta dabaysha oo 33 kV ah ayaa muujiyay 15% impedance distance kadib duufaanta.
Xalka JZP:
Waxay samaysay tijaabada FRA, iyadoo shaaca ka qaadaysa isbeddel sare oo ah heerka sare ee dhawaaqa dhawaaqa 4 kHz.
Waxaa lagu aqoonsaday barokac qayb ahaan wareegaya iyada oo loo marayo sawirka kulaylka 3D.
Ku talinaynaa dib u habeyn, ka hortagga guuldarro masiibo ah oo dhici karta.
- U hoggaansanaanta iyo Shahaadada
Heerarka caalamiga ah: IEC 60076-18, IEEE C57.152.
Shahaadooyinka: CE, UL, ISO 9001.
Ansixinta dhinac saddexaad: Baaritaannada sanadlaha ah ee TÜV Rheinland.
- Gunaanad
Nidaamka ogaanshaha isbeddelka wareegga ee JZP wuxuu isku daraa cabbiraadda saxda ah, falanqaynta AI-ku-saleysan, iyo u hoggaansanaanta buuxda ee DL/T 1093-2018. Iyadoo la isku darayo teknoolojiyada casriga ah sida FRA-ga soo noqnoqda sare iyo warbixinta otomaatiga ah, waxaan hubineynaa in transformers-ku ay si ammaan ah oo hufan uga shaqeeyaan mashaariicda caalamiga ah.