+86 18068001229 Sida Loo Doorto Cabbirka Nidaamka Kaydinta Saliidda Transformer
Hordhac
Codsiyada transformers-ka dhexdhexaadka ah iyo kuwa danab sare leh, nidaamyada haynta saliidda ayaa muhiim u ah ilaalinta deegaanka, u hoggaansanaanta sharciyeed, iyo badbaadada hawlgalka. JZP, waxaan ku takhasusnay naqshadeynta xalalka haynta adag ee loogu talagalay baahiyaha gaarka ah ee transformers-ka warshadaha iyo kuwa heerka adeegga. Tilmaamahan wuxuu qeexayaa tixgelinta muhiimka ah iyo hababka lagu go'aaminayo cabbirka ugu habboon ee nidaamyada haynta saliidda transformer-ka, iyadoo la hubinayo in la waafajiyo heerarka caalamiga ah iyo shuruudaha gaarka ah ee mashruuca.
Qodobbada Muhiimka ah ee Saameynaya Cabbirka Nidaamka Xakamaynta
Mugga Saliidda Isbeddelka
Mabda'a Muhiimka ahNidaamka xakamaynta waa inuu la jaanqaadaa 100% awoodda saliidda ugu weyn ee transformer-kaxaaladaha caadiga ah iyo 110% inta lagu jiro xaaladaha dabka(oo ay ku jiraan biyaha dab-damiska iyo roobabka)
Xisaabinta Tusaale:
Transformer-ka 110 kV oo leh awood saliid oo 30-tan ah (≈34 m³) wuxuu u baahan yahay mugga xakamaynta ee 37.4 m³(34 m³ × 1.1) si loo buuxiyo heerarka badbaadada dabka.
Tixraaca Sharciyeynta:
GB50060-2008wuxuu farayaa in nidaamyada xakamaynta ay Transformer-ka Dibaddas oo leh awood saliid ≥1,000 kg waa inay haysaa60% mugga taangiga ugu weynhaddii la hirgeliyo kala soocidda saliidda iyo biyaha.
Xaaladaha Gaarka ah ee Goobta
Rakibaadda Gudaha iyo Dibadda:
Transformers-ka gudaha (tusaale ahaan, saldhigyada hoose) badanaa waxay u baahan yihiin xakameyn yar sababtoo ah jawi la xakameeyey, halka nidaamyada dibadda ay tahay inay tixgeliyaan roobka iyo carrada u gudubta.
Nadiifinta Badbaadada Dabka:
Hayso a ugu yaraan masaafada 1.5-mitirinta u dhaxaysa transformers-ka iyo darbiyada guban kara, iyo 1 mitir ka baxsan geesaha transformer-kasi loogu kala firdhiyo biyaha dabka
Arrimaha Juqraafiyeed iyo Deegaanka
Awoodda Carrada lagu qaadi karo: Qiimee nooca carrada (tusaale ahaan, dhoobada, quruurux) si loo go'aamiyo xasilloonida aasaaska iyo shuruudaha dheecaanka
Xoogga Roobabka: Nidaamyada bannaanka, xisaabi tabarucaadka roobka adoo isticmaalaya xogta saadaasha hawada ee maxalliga ah (tusaale ahaan, 100 mm/saacaddii gobollada kulaylaha).
Habka Cabbirka Tallaabo-Tallaabo
Go'aami Mugga Saliidda Ugu Badan
Dib u eeg sawirrada farsamada ee transformer-ka si aad u aqoonsato awoodda saliidda ugu weyn (tusaale ahaan, 10,000 litir oo loogu talagalay cutub 60 MVA ah).
Codso Shuruudaha Sharciyeynta
U hoggaansanaanta SPCCRakibaadaha Mareykanka, raac xeerka 110% ee EPA (mugga saliidda + 10% guddiga xorta ah)
Heerarka Shiinaha:
GB50053-2013: Waxay u baahan tahay 20% xakameyn loogu talagalay transformers-yada gudaha ku jira oo leh saliid ≥100 kg ah, taasoo kor u kacaysa 100% haddii dheecaanku aanu shaqaynayn.
Xisaabi Mugga Kaydinta
Qaaciddada:
Gudahawadarta=(Gudahasaliid×1.1)+(Gudahabiyo×0.35)
V_biyo: Mugga biyaha dabka (beerta dusha sare × heerka socodka × muddada).
0.35: Qayb aan waxba tarayn oo ka mid ah waxyaabaha quruuruxdu ka buuxdo (40% daloolo)
Naqshadeynta Transformers-yada Badan
Isugeynta mugga saliidda ee loogu talagalay transformers-yada isku dhafan oo ku dar 20% dhimista ballaarinta mustaqbalka.
Hababka ugu Fiican ee Naqshadeynta Nidaamka Xayiraadda
Xulashada Agabka
Shubka La Xoojiyay: Waxaa loo doorbidayaa isticmaalka gudaha sababtoo ah iska caabbinta dabka iyo cimri dhererka.
Dahaarka Joomatari: Isticmaal dahaarka HDPE meelaha bannaanka ah si looga hortago daadashada ciidda
Qeexitaannada Lakabka Quruurux
Dhumucda: ≥250 mm.
Cabbirka Dhagaxa: Dhexroorka 50–80 mm si loo yareeyo daloolada ugu fiican iyo yareynta dabka
Kala-soocidda Biyaha iyo Saliidda
Ku rakib tuubooyin daloolsan oo leh dhexroor ka badan 150 mm iyo shaashado bir ah oo aan miridh lahayn si aad u shaandhayso wasakhda.
Dhulgariirka iyo Iska caabinta Dabaysha
Naqshadee boolal barroosin ah si aad u adkeysato 0.4 isku-dhafka is-jiidjiidka ee aan joogtada ahayniyo culaysyo gaar u ah aagga dhulgariirka
Gunaanad
Xulashada cabbirka saxda ah ee haynta saliidda transformer-ka waxay u baahan tahay falanqayn taxaddar leh oo ku saabsan mugga saliidda, waajibaadka sharciyeed, iyo xaaladaha goobta. JZP, waxaan ka faa'iideysannaa qalabka injineernimada ee horumarsan iyo dhaqamada ugu wanaagsan ee warshadaha si aan u bixinno nidaamyada haynta oo mudnaanta siiya badbaadada, u hoggaansanaanta, iyo hufnaanta hawlgalka. Nala shaqee si aad u hubiso heerkaaga dhexe iyo kan sareBeddelayaasha Danabka waxaa laga ilaaliyaa daadashada, dabka, iyo khataraha deegaanka.