Fahamka Farsamada iyo Naqshadeynta Isbeddelka Shidaalka ee Saliidda lagu dhex milmay.jpg

Transformer-ka Saliidda lagu dhex milmay Dabayshu waa qaybo muhiim u ah nidaamyada qaybinta korontada, oo loogu talagalay in si hufan loogu wareejiyo tamarta korontada iyadoo la hubinayo isku halaynta iyo waarta. Hoos waxaa ku qoran falanqayn faahfaahsan oo ku saabsan qaab-dhismeedkooda, agabkooda, iyo mabaadi'da hawlgalka, oo laga soo saaray heerarka warshadaha iyo qeexitaannada farsamada.

Heerkulka sare ee qalabka beddelidda saliidda lagu shubo waa mamnuuc inuu dhaafo 95 ° C, guud ahaan waa mamnuuc inuu dhaafo 85 ° C, xulashada guud ee qalabka beddelidda ee lakabka dahaarka fasalka A, heerkulka ugu badan ee la oggol yahay ee qalabka daboolida waa 95 ~ 105 ° C, qeexitaannada kululaynta qalabka beddelidda ee Shiinaha waxay ku salaysan yihiin heerkulka shaqada ee 40 ° C sida caadiga ah, wareegga heerkulka celceliska gaaska ee lagu daray 65 ° C, Kor u kaca heerkulka saliidda sare ee gaaska si sax ah ayaa loogu meeleeyay 55 ° C, sidaa darteed wareegga ay ku jirto xudunta qalabka beddelidda waxaa lagu daray kororka heerkulka saliidda ee 10 ° C.

Haddii heerkulka sare ee qalabka korontadu uu yahay 85 ° C, heerkulka rogrogmada waa 95 ° C; Haddii heerkulka sare uu yahay 95 ° C, heerkulka rogrogmada wuxuu gaaray 105 ° C, kaas oo gaaray heerkulka ugu badan ee la oggol yahay ee qalabka lakabka dahaarka rogrogmada. Heerkulka aadka u sarreeya wuxuu dedejin doonaa gabowga walxaha lakabka dahaarka leh, wuxuu dedejin doonaa burburka saliidda qalabka korontadu leh, wuxuuna dhaawici doonaa cimriga adeegga ee qalabka korontadu leh. Transformer-ka Qaybintas, xitaa waxay horseedaan shilal badbaado.

Nidaam wareeg oo saliid ah oo xooggan oo hawo-qaboojiye ah, heerkul sare 75℃ diirimaad 35℃; Nidaamka wareegga dabiiciga ah ee saliidda, ilaalinta heerkulka xad-dhaafka ah, transformer-ka hawada lagu qaboojiyo, heerkulka sare guud ahaan kuma habboona inta badan ka badan 85 ° C, kuleylka sare ma dhaafi karo 95 ° C kama badnaan karo 55 ° C, haddii laga helo hawlgalka qiimaha xadka ka badan shuruudaha, waa in isla markiiba la soo sheegaa jadwalka wax soo saarka, isticmaalka cabbiraadaha xadka culeyska.

1. ​Qeexidda iyo Shaqada Aasaasiga ah​

Wareegyada isbeddelka ee saliidda ku dhex milmay waxay ka kooban yihiin gariirado naxaas ah ama aluminium ah oo ku wareegsan xudunta birta silicon ee la dahaadhay. Wareegyadan si buuxda ayaa loogu dhex milmay saliid dahaadh ah, taas oo u adeegta laba ujeedo: dahaadh koronto iyo maaraynta kulaylka. Wareegyadu waxay u beddelaan gelinta danab sare wax soo saar danab hoose (ama caksigeeda) iyada oo loo marayo soo-saarid elektromagnetic ah, taasoo suurtogalinaysa gudbinta tamarta oo ammaan ah oo ka gudubta shabakadaha.

2. ​Qaab-dhismeedka Agabka​

Maaddada Gudbinta:

Naxaasta: Waxaa inta badan loo isticmaalaa dabaylaha danab-sare leh sababtoo ah hufnaanteeda sare iyo xooggeeda farsamada. Dabaylaha danab-hoose (≤500 kVA) badanaa waxay qaataan qaab-dhismeed dhululubo ah oo laba-lakab ah, halka awoodaha waaweyn (≥630 kVA) ay isticmaalaan habaynta laba-lakab ama afar-lakab-helix​ si ay u wanaajiyaan qaybinta hadda jirta.

Aluminium: Mararka qaarkood waxaa loo isticmaalaa codsiyada xasaasiga ah ee kharashka, inkastoo ay ka waxtar yar tahay naxaasta.
Dahaarka:

Alaabada iska caabbinta sare leh (tusaale ahaan, resins epoxy, warqad ku salaysan cellulose) waxay ka soocaan daloolada xudunta iyo midba midka kale.

Dahaarka lakabka badan ayaa ka hortagaya wareegyada gaaban ee cadaadiska kulaylka ama isbeddelka farsamada.

3. Naqshadeynta Qaab-dhismeedka

Habaynta Wareegga:

Wareegid Isku-dhafan (Sylindrical) ah: Caadi ahaan transformers-ka saddex-waji leh, halkaas oo wareegyada danab-yaraha lagu dhejiyo gudaha wareegyada danab-sare leh si loo yareeyo qulqulka daadashada.

​Nabarka Lakabka ah (Helical) Wareejinta: Waxaa loo isticmaalaa codsiyada hadda jira ee sare, oo leh lakabyo isku dhafan si loo yareeyo khasaaraha hadda socda.

Is-dhexgalka Qaboojinta:

Dabayshu waxay ku jiraan tuubooyin saliid ah si ay u sii mariyaan kala-baxa kulaylka iyada oo loo marayo qulqul dabiici ah ama qasab ah.

Taangiyada saliidda ee la shiiday ayaa beddelaya kaydadka dhaqanka ee ilaaliya, taasoo u oggolaanaysa ballaarinta kulaylka saliidda iyadoo la ilaalinayo jawi xiran.

4. Hagaajinta Waxqabadka​

Naqshad Lumis Yar:

Xudunta Amorphous Alloy: Yaree luminta hysteresis iyo luminta hadda ee eddy (tusaale ahaan, transformers-ka taxanaha S11-M waxay gaaraan 30% khasaaro ka hooseeya moodooyinka hore)

Kooxda Xiriirka Dyn11: Waxay yareysaa qalloocinta iswaafajinta waxayna hagaajisaa tayada awoodda iyadoo la dhimayo qulqulka iswaafajinta saddexaad

Iska caabinta Wareegga Gaaban:

Qalabka la xoojiyay ee la duubay iyo farsamooyinka la duubay ee wareegsan ayaa xoojiya xasilloonida farsamada inta lagu jiro xaaladaha cilladaha.

Neefsashada jelka silica iyo dib u celinta Buchholz waxay la socdaan cilladaha qoyaanka iyo socodka saliidda.

5. Codsiga iyo Dayactirka​

Xaaladaha Hawlgalka:

Saldhigyada warshadaha, shabakadaha korontada magaalooyinka, iyo nidaamyada tamarta la cusboonaysiin karo (tusaale ahaan, beeraha dabaysha).

Awoodaha la qiimeeyay waxay u dhexeeyaan 50 kVA ilaa 25,000 kVA, iyadoo danabku uu gaarayo 35 kV

Dhaqamada Dayactirka:

Saameynta joogtada ah ee saliidda iyo falanqaynta gaaska milmay (DGA) si loo ogaado burburka dahaarka.

Sawir-qaadista kulaylka si loo aqoonsado meelaha ugu kulul ee ku yaal meelaha wareegsan.

6. Hal-abuurrada Tiknoolajiyada Wareega​

Daadinta Vacuum-ka: Waxay meesha ka saartaa jeebabka hawada inta lagu jiro wax soo saarka, iyadoo hagaajinaysa hufnaanta dahaarka

La socodka Caqliga leh: Dareemayaasha karti u leh IoT waxay la socdaan heerkulka wareegga iyo dhaqdhaqaaqa culeyska waqtiga dhabta ah.