01 Hordhac

Qayb ka mid ah dheecaanka (PD) ee saliidda lagu dhex shubay Transformers-ka Awoodda weli waa caqabad caalami ah oo laga aqoonsan yahay warshadaha isbeddelka. Soo-saareyaal badan ayaa la kulmay khasaarooyin waaweyn oo ka dhashay cillado la xiriira PD.

Xadgudubyada PD-ga ayaa dhici kara inta lagu jiro tijaabinta warshadda, kormeerka dhinac saddexaad, ama goobaha macaamiisha. Helitaanka ilaha PD-ga badanaa waxay la mid tahay "helitaanka irbad ku jirta xero caws," taasoo horseedaysa dib-u-shaqayn maalmo ama xitaa bilo socota, taasoo keenta khasaare tayo oo weyn oo soo saarayaasha ama dadka isticmaala dhammaadka.

Sidaa darteed, cilmi ahaan loo ogaado oo si dhakhso ah loo aqoonsado sababaha keena PD xad-dhaafka ah waa muhiim.

02 Qeexidda iyo Dabeecadda

In kasta oo aanu jirin qeexitaan rasmi ah, qoraagu wuxuu PD ku qeexayaa sidan:
[Ka daadashada waxay ka dhacdaa boosas ku meel gaar ah oo ku jira transformer-ka kaas oo aan weli sababin burbur degdeg ah oo ku yimaada dahaarka ama iftiinka.]

Xaaladaha PD aad bay u kala duwan yihiin laakiin waxay wadaagaan nuxur guud:
[Cillado qaab-dhismeed, agab, ama wax-soo-saar oo ku jira nidaamka dahaarka ayaa sababa qallooc ku yimaada goobta korantada ee maxalliga ah oo ka badan xoogga dielectric-ka ee waqtigaas, taasoo keenta burbur soo noqnoqda, oo yar-yar, oo aan gelinayn ionization.]

Marka la soo koobo, dabeecadda PD waxay ku jirtaa uruurinta goobta korantada ee maxalliga ah oo ka sarreysa xoogga goobta bilowga PD.

03 Sababaha ugu Muhiimsan

Iyada oo ku saleysan hababka PD, wax kasta oo sababa goobaha korantada ee xad-dhaafka ah ee maxalliga ah waxay kicin karaan xad-dhaafka PD.

3.1 Goobaha PD
PD waxay ka imaan kartaa:

Bushings

 

Beddelayaasha tuubada OLTC/DETC

 

Hogaamiyeyaasha

 

Dabayl

 

Qaybaha dhulka

 

Dusha sare ee dahaarka/ciladaha gudaha

 

Saliidda Transformer-ka

Goobaha ugu nugul:Hulalka hawada ee ku jira dahaarka adag ama xumbo gaas ah oo ku jira saliidda.
Sababta:Marka la eego cadaadiska danab, xoogga goobta korontada ayaa si liddi ku ah u dhigma joogtada dielectric (ε).

Dahaarka warqadda ε ≈ 4.4

 

Madhannada hawada ε ≈ 2.0
→ Hulalka hawada waxay la kulmaan xoog sare oo goobta ah oo ah ≈2.2×.
Iyada oo leh xoog jab yar (AC ≈2kV/mm), godadka/xumbo waxay noqdaan meelo daciif ah oo loogu talagalay bilowga PD.

3.2 Noocyada PD
Noocyada caadiga ah ee PD ee ku jira Transformer-ka Saliidda lagu dhex milmays:

Daadinta xumbo gaas

 

Daadinta qoyaanka keenta(dahaarka qoyan)

 

Daadinta elektroodka fiiqan(talooyin elektroodh koronto sare/dhul leh)

 

Daadinta suurtagalka ah ee sabeynaya

 

Daadinta farqiga saliidda ee qaab-dhismeedka ah

 

Daadinta walxaha birta/wasakhaysan

 

Cilladaha dhejiska(xabag tayo sare leh/tayo liidata oo ku jira saxamada isku dhejinta/giraanta dhammaadka)

Aragti Muhiim ah:

Xadgudubka PD-ga si dhif ah ayuu ula xiriiraa nashqadeynta (≈0.5% suurtogalnimada).
95%+ asal ahaan waxay ka timid cillado agab, hab-raac, ama wax-soo-saar.

Sababta:Marka danabyada xad-dhaafka ah (LI, LIC, SI, LTAC) loo beddelo danab u adkaysta awoodda-soo noqnoqoshada 1-daqiiqo (Beddelka DIL), dhammaantood waxay dhaafeen danabka tijaabada PD (IVPD). Dahaarka ugu weyn/dheer waxaa loogu talagalay xaaladda danabka xad-dhaafka ah ee ugu sarreeya.

Maya.

Nooca PD

Goobta

Habka

Kiisaska Caadiga ah

1

Daadinta Elektrode-ka Fifsan

Qaybaha isku xidhka, taangiga, bushing-ka kor u kaca, terminaalka crimping-ka ee rasaasta

Gacan yar oo qalooc ah → cufnaanta dallacaadda sare → fiirsashada goobta aadka u daran

Boolal aan gaashaan lahayn oo u dhow elektroodhada HV; geesaha fiiqan ee ku yaal gaashaanka birlabta

2

Dheecaanka Gaaska/Madhanka

Xumbo saliid ah / godad ku jira dahaarka adag

Joogto dielectric hooseeya (ε≈1) → cadaadis sare oo goobta ah + xoog jab yar (2kV/mm)

Faakiyuum aan dhammaystirnayn; buuxinta saliidda degdega ah; dhejis xad-dhaaf ah/liita oo ku jira giraanta dhammaadka/goobaha isle'egta

3

Daadinta Qoyaanka oo ay keento

Dabaylaha, dahaarka xudunta, raadadka

Qoyaanku wuxuu yareeyaa xoogga dielectric 60-70%

Qallajin aan ku filnayn oo xudunta ah; u-soo-gaadhis xad-dhaaf ah hawada ku xeeran inta lagu jiro isku-dubaridka

4

Daadinta Suurtagalka ah ee Sabaysan

Saxanka cadaadiska, taageerada rasaasta, shunts-ka birlabta ah

Isu ururinta dallacaadda → garaaca degdegga ah ee dheecaanka

gaashaan birlab ah oo aan dhulka ku jirin; faraantiyo koronto-ku-saleysan oo si liidata isugu xiran

5

Daadinta Wasakhaysan

Biyo/faybar/qaybo bir ah oo saliid ku jira

qallooca goobta + biyuhu waxay kordhiyaan cadaadiska goobta 2.9×

Shaandheyn saliid oo aan ku filnayn; xudunta wasakhaysan; qoyaan soo galaya

04 Aragtida

Fahmidda noocyada caadiga ah ee PD, farsamooyinka, goobaha, iyo daraasadaha kiisaska ayaa lagama maarmaan u ah xallinta dhibaatooyinka la beegsanayo.

Marka lagu daro mabaadi'da isku xirka isbeddelka, naqshadeynta qaab-dhismeedka, astaamaha mowjadaha PD, deegaanka polarity-ga, iyo tijaabooyinka ogaanshaha, aqoontani waxay suurtogal ka dhigaysaa aqoonsashada sababta xididka oo degdeg ah waxayna yaraynaysaa khasaaraha tayada.